Technical Features
Output signal: three ways 4...20mA, three ways 0...10V or RS485
Output parameter: temperature, relative humidity, pressure difference
Shell material: flame-retardant PC
Calibration interface: single-point or two-point calibration via configuration port
Installation method: temperature and humidity split probe
Display module: fixed display
Digital probe: interchangeable digital probe for easy on-site maintenance
Typical Applications
Electronic semiconductor clean room Biopharmaceutical clean room Tobacco process workshop
Clean room for printing money High standard laboratory
Technical Data
Input and output
Operating voltage
|
18...30V DC
|
|
Current output
|
Three ways 4... 20mA RL < 500 Ohm
|
Power consumption
|
<20mA (current output)
|
|
Voltage output
|
Three ways 0...10V
|
|
< 6mA (digital output)
|
|
|
Channel precision: ±0.2%FS
|
|
|
|
Digital output
|
RS485 (Modbus RTU)
|
Measurement Parameter
Relative humidity
|
|
|
Temperature
|
|
Measurement range
|
0 ... 100%RH
|
|
Measurement range
|
−40 … +80°C
|
Measurement precision
|
±1%RH (0 … 90%RH & 20℃)
|
|
Measurement precision
|
±0.2°C
|
Calibration error
|
±0.5%RH (0 … 90%RH)
|
|
Calibration error
|
±0.1°C (20°C)
|
|
±0.8%RH (40 … 95%RH)
|
|
|
|
τ63 response time
|
30s (probe fitted with stainless steel sintered filter)
|
|
- -
|
- -
|
Humidity sensitive element
|
High molecular polymer humidity-sensitive capacitor
|
|
Temperature sensitive element
|
Pt1000 (Grade 1/3B, DIN EN 60751)
|
|
|
|
Pressure difference
|
|
|
|
Measurement range
|
0 ... ±50pa to 0 ... ±10Kpa (optional)
|
|
Sensor
|
piezoresistive pressure difference sensor
|
Measurement precision
|
A1: ±0.5%FS (FS indicates full scale)
|
|
τ63 response time
|
30ms
|
|
A2: ±1%FS
|
|
Temperature characteristics
|
< 0.03 % FS/℃
|
|
A3: ±1.5%FS
|
|
Sampling frequency
|
15s
|
Overload pressure
|
10Kpa (0 ... ±1000pa)
|
|
Temperature compensation
|
0 ... 60℃
|
|
80Kpa (0 ... ±10Kpa)
|
|
|
|
The above precisions are comprehensive precisions, including repeatability, linearity and hysteresis of the measurement, and can be traced to the CNAS standard.
Technical Specification
Wiring connection
|
The maximum cable diameter of the terminal is 1.5mm2
|
|
Cable connector
|
M16*1.5 gland connector (threading diameter 4.5~10mm)
|
Shell material
|
PC (flame-retardant grade UL94-V0) or Aluminium alloy (optional)
|
|
Protection grade
|
IP65
|
Operating temperature
|
With display: -40 ... 80℃
|
|
Probe protection
|
Stainless steel sintering, H2O2, PTFE, etc.
|
|
Without display: -20 ... 80℃
|
|
Electromagnetic compatibility
|
EN61326-1 EN61326-2-3
|
Storage temperature
|
-20 ... 60℃
|
|
|
|
Data download:
THP130 Clean Industrial Temperature and Humidity Pressure Difference Transmitter Product Manual