VT210 Industrial Grade Pressure-Difference Flowmeter for Wind Volume and Mass

The monitoring of wind speed and wind volume in air conditioning pipes in clean industries such as biopharmaceuticals and electronic semiconductors can not only ensure the normal operation of the air conditioning system, but also effectively control the operation energy consumption. VT210 is a pressure difference principle-based wind volume transmitter with temperature compensation function, fitted with the average wind speed gauge installed in the air conditioning pipe.

At present, similar products based on the principle of single point wind speed measurement have very high requirements for the installation of straight pipe sections. For example, the straight pipe section of air conditioning is too short or the distribution of air fluid is irregular turbulence in the position of elbow pipe and valve accessories, so stable and effective wind volume cannot be measured. Thanks to VT210 average wind speed gauge, the multi-point wind speed in the same section of the air conditioning pipe is collected and averaged, which has relatively low requirements for the straight pipe section and installation position, and can also ensure the accurate measurement of wind volume, so it is very suitable for the complex air conditioning pipe conditions on site.

    In addition, using the integrated algorithm, VT210 can calculate the standard condition volume flow and mass flow of the gas medium in the pipe through the cross-sectional area of the pipe, the standard condition density of the gas medium and the temperature compensation algorithm, and the temperature range of the measured gas can reach -40~300℃.

Technical Features

Piezoresistive sensor

Display optional

Multiple output signals

Zero calibration

Typical Applications

Biopharmaceuticals and Electronic semiconductor 

High standard clean room

Building automation and control

Filter monitoring

Technical Data

Input and output

Operating voltage

24V DC±20%

 

Current output

4 ... 20mA  RL < 500 Ohm

Power consumption

Current output: < 15mA (typical value)

Voltage output

... 5V; 0 ... 10V

 

Voltage output: < 10mA 

 

Channel precision: ±0.2%FS

 

RS485 digital output: < 10mA 

Digital output

RS485 (Modbus RTU)

Measurement Parameter

Wind speed measurement range

3...100m/s (9 ... 10000Pa)

 

Sensor

Piezoresistive pressure difference sensor

Measurement precision  

±2% measurement value (wind speed > 3m/s)

 

τ63 response time

30ms

Overload pressure

10Kpa (0 ... ±1000pa)

Temperature characteristics

< 0.03%FS/℃

 

 

80Kpa (... ±10Kpa)

Sampling frequency

15s

Temperature compensation

0 ... 60℃

 

 

The above precisions are comprehensive precisions, including repeatability, linearity and hysteresis of the measurement, and can be traced to the CNAS standard.

Technical Specification

Wiring connection

The maximum cable diameter of the terminal is 1.5mm2

 

Shell material

PC (flame-retardant grade UL94-V0)

Cable connector

M16*1.5 gland connector (threading diameter 4.5~10mm)

 

Protection grade

IP65

Operating temperature and humidity

-20 ... 85℃  0 ... 95%

 

Electromagnetic compatibility

EN61326-1  EN61326-2-3

Storage temperature

-20 ... 60℃

 

Display module

Field LCD display

Data download: 

VT210 Industrial Grade Pressure-Difference Flowmeter for Wind Volume and Mass Product Manual







Copyright © GemCreate Electronics Technology (Shanghai) Co., LTD. All Rights Reserved.
Complaint feedback
Welcome feedback, your suggestion is our motivation!
We will carefully review each question you have feedback and give you the first reply.
Name:
Contact:
Content: